Analog Earth Resistance: AER-13505
Digital Earth Resistance: DER-13520
Analog Earth Leakage Tester: AEL-13810
Digital Earth Leakage Tester: DEL-13820
Analog Insulation Testers: AIT-13503 | AIT-13504 | AIT-13800 |
Digital Insulation Testers: DIT-03200 | DIT-13210 | DIT-13212 | DIT-13550 | DIT-13804
| Digital Insulation Tester: DIT-03200 |
![]() |
| FEATURES : |
| *Digital display |
| *0.7" large LCD display |
| *Portable, battery operated |
| *Wide measuring range & high accuracy |
| *LSI- circuit provides high reliability and durability |
| *Built-in over-input and low-battery indication |
| *Overload protection for each range |
| *Sensitive Ohm meter scale 0~200 Ohm for low resistance measurement such as motor windings, relay coils etc. |
| *Durable ABS plastic case |
| *Multi-range with 0 ~200M Ohm/500V and 0~1000M Ohm/1000V |
| *Rezero adjustment and automatic circuit discharge |
SPECIFICATIONS:
| Sampling Time | 0.4 sec | |||
| MW Response Time | Max. approx. 2.5 sec | |||
| Over-input | Display "1" | |||
| Operating Temp. | 0 ~ 122 F | |||
| Operating Humidity | Less than 80% RH | |||
| Power Supply | DV 12V( 1.5V AA battery) | |||
| Power Consumption | Approx. 100 mA (1000 MW/1000V range) | |||
| Approx. 50 ma (200 MW/500V range) | ||||
| Approx. 1.6 ma (200 W/OHMS range) | ||||
| Dimensions | 6.7" x 5" x 3.1" | |||
| Weight | 1.2 lbs | |||
| Meg Ohm | ||||
| Range | Accuracy | Resolution | Open circuit Voltage | Short Circuit Current |
| 200 MW (500V) | +/- (3% + 1d) | 0.1MW |
Approx. 480V(>7MW) Approx. 475 V(5~7MW) |
Approx. 0.4 ma |
|
1000 MW (1000V) |
+/- (3% + 1d) | 1MW |
Approx. 980V(>7MW) Approx. 950 V(5~7MW |
Approx. 0.7mA |
| OHMS | ||||
| Range | Accuracy | Resolution | Open circuit Voltage | Overload circuit protection |
| 200W | +/- (1% + 1d) | 0.1W | Approx. 3V | AC/DC 500V (within 20 sec) |
Standard accessory: Alligator Clips
Copyright 2000-2013 Sun Equipment Corporation. Prices and specifications are subject to change without notice